Decide what must stay powered during an outage and what should shut down. A UPS needs enough output for those devices, enough battery time for that plan, and a supported way to tell the equipment that utility power has failed.
Size both watts and volt-amps
List every device that needs battery power, including the switch or router needed to carry shutdown messages. Check the equipment's actual demand during the work it will do, and keep the total within both the UPS watt limit and its separate volt-amp limit. A computer power supply's maximum rating is not a measurement of its normal draw.
The current US CyberPower CP1000PFCLCD is rated at 1000 VA and 600 W. The reviewed CP1500PFCLCD 1000 W version is rated at 1500 VA and 1000 W. APC BR1500MS2 is also 1500 VA but has a 900 W limit. Matching the VA number alone would miss that difference. None of these output ratings tells you how many minutes the battery will last.
Leave capacity for changing demand and follow the exact model's installation restrictions. CyberPower's manuals exclude high-demand appliances such as space heaters and laser printers from the battery-backed outlets. This category covers US 120 V desktop AC units; check the plug, voltage and model revision before using another region's listing as a substitute.
Compare runtime at the same absolute load
A half-load figure changes meaning with the UPS rating: half of 600 W is 300 W, while half of 1000 W is 500 W. Use the same stated watt load for both candidates and retain the manufacturer's conditions.
- At 100 W, CyberPower's current estimates are 30 minutes for CP1000PFCLCD and 66 minutes for the reviewed CP1500PFCLCD.
- At 200 W, the corresponding estimates are 13.5 and 30.8 minutes.
CyberPower describes these as estimates for fully charged, new batteries under normal conditions. Battery age, charge and environment can change the result; the reviewed explanation does not specify a numeric ambient temperature or load power factor. These figures support a comparison of the manufacturer's estimates, not a promise for an installed NAS or computer.
Choose a shutdown delay that leaves time to finish the stop and retain reserve. If your load differs from a published point, read the manufacturer's calculator at that load or leave the runtime unresolved. Do not scale a runtime in proportion to VA, watts or battery amp-hours. CompareFoundry has not measured these units' runtime.
Count the outlets that stay powered
The reviewed CP1000PFCLCD has five battery-backed outlets and five surge-only outlets. CP1500PFCLCD has six of each; BR1500MS2 has six backed outlets and four surge-only outlets. Their US AC receptacles are NEMA 5-15R. The total socket count does not tell you how many devices will remain powered.
Map each critical device to a battery-backed outlet, then check the space needed by its plug or power adapter. Include networking equipment if another device depends on it for shutdown messages. Surge-only outlets protect against specified surges but do not keep that equipment running through a loss of utility power.
Measure the body, cable exits and ventilation space separately. A manufacturer's shipping dimensions are not the UPS footprint, and the body dimensions alone do not establish an installed fit. BR1500MS2's current manual has inconsistent inch and metric dimensions, so those observations remain unresolved rather than becoming a confident fit recommendation.
Read waveform, regulation and transfer time separately
The reviewed CyberPower units and BR1500MS2 are line-interactive UPS models with sine-wave output on battery. Automatic voltage regulation handles specified input-voltage variation; it does not establish unlimited tolerance or zero interruption during a switch to battery.
CyberPower specifies a typical transfer time of 4 ms for these two models. A typical figure is not a maximum. For BR1500MS2, the live US listing gives 8 ms typical and 10 ms maximum, while its April 2026 manual says 8 ms maximum. We retain that disagreement. A transfer-time label is not proof that every connected power supply will ride through an outage.
Connect a data cable and verify shutdown support
The CyberPower models document a rear USB HID monitoring connection and include a USB A-to-B data cable. Their front USB-A and USB-C sockets are charging outputs. APC's manual likewise distinguishes its supplied USB communication cable at the rear Data Port from its front charging ports. Plugging a NAS into an AC outlet or charging socket does not configure automatic shutdown.
Keep three questions separate: does the UPS manufacturer document a data protocol; does the computer or NAS vendor support that exact UPS and software combination; and has the installed setup completed an outage-and-restart test? A vendor compatibility entry is useful evidence, but it does not test your battery, cables, firmware or shutdown settings. A historical driver report may describe a different revision. An absent listing is unresolved evidence, not proof of incompatibility.
For network management, the reviewed CP1500PFCLCD documents an optional RMCARD205. It is not included in the base purchase. Ethernet surge-protection sockets are a different feature and do not provide that management function. Check the protocol and software support at both ends before buying an accessory.
Our NAS power and graceful-shutdown guide explains USB and network arrangements, protected states, shutdown order and restoration checks. Follow the device and UPS manuals for a controlled test, and repeat the relevant checks after changing the battery, load or settings.
Read the NAS compatibility evidence by model
On 2026-10-03, Synology's UPS compatibility list marked CP1000PFCLCD, CP1500PFCLCD and APC Back-UPS Pro BR1500MS2 as Vendor Recommended. These entries were not labelled Synology-tested. Each inspected detail included DS425+, DS925+ and DS223j, but did not identify the UPS hardware revision, NAS operating-system version or test conditions.
| Reviewed UPS | QNAP list observation | Network UPS Tools evidence |
|---|---|---|
| CP1000PFCLCD color-LCD version | The CP1000PFCLCD USB 2.0 entry includes TS-264 and TS-464. Its UPS revision is unstated. | Historical usbhid-ups reports describe a 600 W CP1000PFCLCD. That matching rating does not identify the current color-LCD revision. |
| CP1500PFCLCD 1000 W version | The CP1500PFCLCD USB 2.0 entry includes TS-264. The entry does not identify the current 1000 W revision. | Historical reports using NUT 2.7.1 and 2.7.4 describe 900 W hardware. They do not establish testing of this 1000 W version. |
| APC BR1500MS2 | The exact BR1500MS2 was not found in the reviewed APC list. BR1500MS-TW was listed, but is a different SKU. | The exact MS2 was not found in the reviewed hardware compatibility list. APC USB family-level evidence does not identify this model. |
These dated observations help choose what to verify next; they do not establish that a particular installation has completed shutdown and restart. A missing entry leaves support unresolved, rather than proving incompatibility. Confirm the exact delivered UPS, NAS software and connection, then follow the controlled test in the NAS guide.
Match the replacement battery to the delivered unit
User-replaceable does not mean one cartridge fits every device with a similar name. CyberPower lists RB1290 for the reviewed CP1000PFCLCD. Its CP1500PFCLCD documentation maps RB1290X2 to serial numbers beginning CXX and RB1280X2B to CR9, CXF or CQC. Check the label on the delivered unit before ordering a replacement; the shop listing alone cannot reveal its serial prefix.
APC lists APCRBC163 for BR1500MS2. Follow the exact replacement procedure and disposal instructions. Battery condition affects runtime, so a replacement plan and a successful shutdown test matter alongside the initial output rating.
Use the UPS comparison to keep exact US packages, source limitations and manufacturer runtime estimates together. Confirm the selected revision and supplied accessories before ordering.
Common questions
Does a 1500 VA UPS always provide more watts than a 1000 VA unit?
Check both ratings on the exact model. The reviewed CP1000PFCLCD is 1000 VA / 600 W, CP1500PFCLCD is 1500 VA / 1000 W, and APC BR1500MS2 is 1500 VA / 900 W. VA alone neither fixes the watt limit nor establishes runtime.
Will a USB charging port shut down my NAS automatically?
No. A charging output supplies power. UPS status needs a supported data connection, compatible software and configured shutdown behavior. Verify the exact NAS and UPS combination, then test the installed setup using the manufacturers' procedures.
Are the runtime figures guaranteed for my equipment?
No. They are manufacturer estimates at a stated load. Battery charge, age, temperature and connected equipment affect the result. Use the same load when comparing estimates and leave time and battery reserve for shutdown.
CyberPower CP1000PFCLCD runtime calculator · CyberPower CP1500PFCLCD runtime calculator
Sources & further reading
- CyberPower CP1000PFCLCD current US model and runtime calculatorChecked 2026-10-03
Color-LCD 1000 VA / 600 W, ten-outlet unit. The directly reviewed calculator gives 30 minutes at 100 W and 13.5 minutes at 200 W for fully charged new batteries under normal conditions; numeric ambient and load power factor are unspecified.
- CyberPower CP1500PFCLCD current 1000 W US model and runtime calculatorChecked 2026-10-03
1500 VA / 1000 W, twelve-outlet version. The directly reviewed calculator gives 66 minutes at 100 W and 30.8 minutes at 200 W with the same stated battery conditions. A reused model name does not establish identical older hardware.
- CyberPower CP1000PFCLCD current data sheetChecked 2026-10-03
Output ratings, outlet split, sine-wave output, AVR, typical transfer time, HID data interface and RB1290 cartridge. The sheet has conflicting half/full-load runtime summaries; those are not substituted for the reviewed absolute-load calculator points.
- CyberPower CP1500PFCLCD 1000 W data sheetChecked 2026-10-03
Exact 1000 W / twelve-outlet configuration; optional RMCARD205, 4 ms typical transfer and serial-prefix-specific replacement battery mapping.
- CyberPower CP850PFCLCD / CP1000PFCLCD manualChecked 2026-10-03
Box contents include the USB A-to-B cable. Installation and rear data connections are separate from USB charging and Ethernet surge protection.
- CyberPower CP1350PFCLCD / CP1500PFCLCD manualChecked 2026-10-03
Box contents and operating instructions for the reviewed 1000 W version; optional network-management slot is separate from protected Ethernet sockets.
- Synology UPS compatibility list: vendor recommendationsChecked 2026-10-03
Rendered rows and View details reviewed on 2026-10-03. CP1000PFCLCD, CP1500PFCLCD and APC Back-UPS Pro BR1500MS2 were Vendor Recommended, not labelled Synology-tested; each inspected detail included DS425+, DS925+ and DS223j. UPS revision, NAS OS version and test conditions were unstated.
- QNAP recommended UPS models: CyberPowerChecked 2026-10-03
Rendered USB 2.0 entries and expanded model lists reviewed. CP1000PFCLCD included TS-264 and TS-464; CP1500PFCLCD included TS-264. No claim is made here about TS-464 with CP1500PFCLCD. Exact UPS hardware revisions were unstated.
- QNAP recommended UPS models: APCChecked 2026-10-03
Exact BR1500MS2 was not found in the inspected list; BR1500MS-TW was present and remains a separate SKU. Absence from this observation is not an incompatibility finding.
- Network UPS Tools CP1000PFCLCD device reportsChecked 2026-10-03
Historical usbhid-ups reports identify 600 W hardware. The matching rating does not prove the current color-LCD revision was tested, or establish any particular NAS firmware or shutdown configuration.
- Network UPS Tools CP1500PFCLCD device reportsChecked 2026-10-03
Reports using NUT 2.7.1 and 2.7.4 identify 900 W hardware. They are not evidence of testing the reviewed current 1000 W / twelve-outlet generation.
- Network UPS Tools hardware compatibility listChecked 2026-10-03
Exact BR1500MS2 was not found; APC USB family-level evidence is retained at that scope. No model-specific support or incompatibility conclusion follows from it.
- APC BR1500MS2 official US listingChecked 2026-10-03
1500 VA / 900 W, six battery-backed and four surge-only outlets. Its 8 ms typical / 10 ms maximum transfer claim differs from the current manual.
- APC Back-UPS Pro 120 Vac manual, EN JPT92208, April 2026Checked 2026-10-03
Pages 6 and 8–9 identify the supplied USB communication cable and distinguish data from charging and protected Ethernet sockets. Pages 16–17 cover ratings and APCRBC163. The 8 ms maximum transfer claim conflicts with the US page; inch and metric body dimensions are inconsistent.
See our methodology for source labels and limitations. Product evidence dates are shown beside the corresponding specifications.
Suggest a correction